Permit: T19CM09145

Parcel: 136333240


Addresses:

8961 E DOLORES ST


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T19CM09145

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/06/2020 MECHANICAL - FINAL Approved
12/17/2019 MECHANICAL - FINAL Partial Approval Provide 20 amp minimum GFI protected service receptacle on roof within 25 feet of equipment, receptacle to have own circuit.