Permit: T19CM08918

Parcel: 119220820

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
02/18/2020 PLUMBING - GAS PRESSURE TEST Approved Clear gas meter
12/13/2019 PLUMBING - GAS PRESSURE TEST Denied 1- Shall revise the approved drawing to reflect the BBQ Grill and Range supply that has been added.
2- Shall provide (3) sheet metal screws per joint on water heater flex connector and draft collar.
3- Shall seal the gas line penetration at exterior wall.
4- Shall provide gas shut off valves for the range and bbq.