Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T19CM08842
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/17/2020 | ELECTRIC - FINAL | Approved | Clear TEP DGC | |
06/08/2020 | ELECTRIC - FINAL | Denied | denied 1- Service panel is existing and does not have a main switch. There are over 6 circuit breakers on panel therefore a main switch is required on panel. 2- Shall revise the plan to reflect the main switch size to back feed circuit breaker and solar system. |
|
04/28/2020 | ELECTRIC - FINAL | Denied | 1- The approved plans do not show the circuit breaker size. Shall provide a revised and approved plan showing this circuit breaker. | |
04/27/2020 | ELECTRIC - FINAL | Not ready for Inspection | RVI Not ready. Cancelled by contractor... will reschedule |