Permit: T19CM08806

Parcel: 137293570


Addresses:

1751 W TENNYSON DR

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
12/09/2019 PLUMBING - FINAL Approved
12/04/2019 PLUMBING - FINAL Denied 1- Shall make all necessary repairs or replacement of the cut electric conductor at the Dining and Kitchen entry by a licensed electric contractor.
2- Shall provide verification of fire rated foam used for the top plate penetrations.
3- Shall secure all horizontal piping every 32 inches and every 4 feet vertically. Lots of loose piping throughout the system.
4- Shall provide the required shielded plates on all top plate penetrations.
5- Shall secure the water heater flu vent to the draft collar with (3) sheet metal screws.
6- Shall provide 8 feet of insulation on the water heater hot supply line.
7- Angle stops under the cabinets are loose.