Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/09/2019 | PLUMBING - FINAL | Approved | ||
| 12/04/2019 | PLUMBING - FINAL | Denied | 1- Shall make all necessary repairs or replacement of the cut electric conductor at the Dining and Kitchen entry by a licensed electric contractor. 2- Shall provide verification of fire rated foam used for the top plate penetrations. 3- Shall secure all horizontal piping every 32 inches and every 4 feet vertically. Lots of loose piping throughout the system. 4- Shall provide the required shielded plates on all top plate penetrations. 5- Shall secure the water heater flu vent to the draft collar with (3) sheet metal screws. 6- Shall provide 8 feet of insulation on the water heater hot supply line. 7- Angle stops under the cabinets are loose. |