Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/05/2020 | ELECTRIC - FINAL | Approved | RVI | |
| 01/29/2020 | ELECTRIC - FINAL | Correction Required | RVI ENTIRE SYSTEM IS WIRED WITH GREEN WIRE. THIS MUST BE REPLACED WITH PROPERLY COLOR CODED WIRES. ALL ENDS OF CONDUIT MUST HAVE BOND BUSHING INSTALLED AND GROUND WIRE CONNECTED. BACK FEED BREAKER MUST BE LOCATED AS FAR FROM MAIN BREAKER AS POSSIBLE. |