Permit: T19CM08110

Parcel: 11918027A


Addresses:

1302 W AJO WY #388

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
11/14/2019 MECHANICAL - FINAL Approved
11/13/2019 MECHANICAL - FINAL Denied 1- Shall provide locking caps on the condenser refrigerant service ports
2- Shall secure the liquid tight electric whip to the condenser.
3- Condenser fuses are the wrong size of amps.