Permit: T19CM07824

Parcel: 137050700


Addresses:

433 W LOUISIANA ST

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
12/09/2019 PLUMBING - GAS PRESSURE TEST Approved
12/06/2019 PLUMBING - GAS PRESSURE TEST Denied 1- Shall provide a gas ground bond on the system.
2- Shall provide the correct and required test gage.
3- Shall provide a minimum of 1 inch clearance from combustible material for the water heater flu vent.
4- Shall terminate the water heater t & p drain 6 inches above grade.
5- Shall seal the penetration to the Range.