Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/20/2022 | FIRE - FINAL | Approved | ||
| 02/05/2020 | FIRE - FINAL | Partial Approval | OK FOR TCO TO OCCUPY. Still need items from 01/31/2020 | |
| 02/03/2020 | FIRE - FINAL | Denied | None of the items from list on 1/31/2020 have been completed at 2:15pm arrival. | |
| 01/31/2020 | FIRE - FINAL | Partial Approval | Need F.A.C.P room sign X 1 Need RISER ROOM sign X 2 Front door lock needs to meet IFC, 1010.1.9.4 Remova all abandoned fire alarm devices and wires OK for TCO to fund no occupancy until the elevator is apporved OK for TCO to occupy once elevator passes the inspection and paperwork submitted to PDSD. |