Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
Permit Number - T19CM07441
Inspection Description - ELECTRIC - RECONNECT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/18/2019 | ELECTRIC - RECONNECT | Approved | Clearance TEP RECN. | |
10/17/2019 | ELECTRIC - RECONNECT | Correction Required | 1-Seal all unused openings in electrical system. 2 -Bond water piping, and gas piping. |
|
10/14/2019 | ELECTRIC - RECONNECT | Correction Required | 1- Grounding Electrode Conductor has been removed; ground service per Code, to include water and gas piping requirements. 2-Exterior wiring is exposed; remove or cover per Code. |