Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
Permit Number - T19CM07406
Inspection Description - MECHANICAL - FINAL
Inspection Status - Denied
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/22/2020 | MECHANICAL - FINAL | Denied | EXHAUST FLOW RATE FOR EF-1 NOT PER PLANS (32% LOW) | |
| 07/22/2020 | MECHANICAL - FINAL | Approved | REVIEW OF AIR BALANCE REPORT COMPLETED | |
| 07/15/2020 | MECHANICAL - FINAL | Denied | OSA FOR HP-1 & EXHAUST FLOW RATE FOR EF-1 NOT PER PLANS | |
| 07/14/2020 | MECHANICAL - FINAL | Partial Approval | Partial. Pending air balance report. | |
| 07/10/2020 | MECHANICAL - FINAL | Denied | Denied. Called contact number, no message. Please call your inspector for further information. | |
| 11/06/2019 | MECHANICAL - FINAL | Prior to Final Inspectn | AIR BALANCE REPORT REQUIRED |