Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T19CM07404
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/22/2020 | FIRE - FINAL | Approved | -Label breakers in electric panels -Cover open breaker slot |
|
01/10/2020 | FIRE - FINAL | Prior to Final Inspectn | These are notes only from observations made during hood inspection. Needs full fire final inspection. -obtain operational permit for POA -mount OL sign -number the hoods and pull stations -mount extinguishers (K and ABC's) -north outlet behind fryers needs to also be on shunt trip -electric outlet to pizza oven needs to be on shunt trip -remove tank and pull station from hood #3. hood is not being used. gas valve shuts off gas to all three hoods. |