Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Passed
Inspection History: COT - RSEL - Service Upgrade
Permit Number - T19CM07358
Inspection Description - COT - RSEL - Service Upgrade
Inspection Status - Passed
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/04/2019 | COT - RSEL - Service Upgrade | JCLAXTON | Approved | Entered by SFLORES2 - |
| 11/27/2019 | COT - RSEL - Service Upgrade | MRAMBER | Not ready for Inspection | Entered by DMERANZ1 - Roof jack required at riser through roof. Gas bond to be on house side of meter, downstream of all dielectric unions. |
| 11/22/2019 | COT - RSEL - Service Upgrade | RCHANDLER | Correction Required | Entered by DMERANZ1 - Grounding Electrode Conductor must run continuously from service to one of the electrodes; can not be a separate one for each ground rod. |