Inspection Status: Passed
Inspection History: COT - RSEL - Service Upgrade
| Date |
Description |
Inspector |
Results |
Comments |
| 12/04/2019 |
COT - RSEL - Service Upgrade |
JCLAXTON |
Approved |
Entered by SFLORES2 - |
| 11/27/2019 |
COT - RSEL - Service Upgrade |
MRAMBER |
Not ready for Inspection |
Entered by DMERANZ1 - Roof jack required at riser through roof. Gas bond to be on house side of meter, downstream of all dielectric unions. |
| 11/22/2019 |
COT - RSEL - Service Upgrade |
RCHANDLER |
Correction Required |
Entered by DMERANZ1 - Grounding Electrode Conductor must run continuously from service to one of the electrodes; can not be a separate one for each ground rod. |