Permit: T19CM07329

Parcel: 130021070


Addresses:

1635 S TREAT AV

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
02/04/2020 MECHANICAL - FINAL Approved
10/11/2019 MECHANICAL - FINAL Denied 1- Shall extend and terminate the condensate drain line a minimum of 6 inches above sub grade.
2- Shall provide protection on for the condensate drain and properly secure the line on blocking.
3- Shall provide a sediment trap on gas supply.
4- Shall secure the liquid tight electric whip to the unit.
5- Shall provide access to the roof at the time of inspection request.