Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 11/05/2019 |
ELECTRIC - FINAL |
|
Approved |
|
| 10/21/2019 |
ELECTRIC - FINAL |
|
Denied |
Corrections not made, another failed inspection will result in a reinspection fee. |
| 10/18/2019 |
ELECTRIC - FINAL |
|
Denied |
Ground rods not properly installed, ground rods not to be installed diagonally. grounding conductors run through EMT must be bonded at both ends, provide two points of attachment to the structure at riser |