Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 10/24/2019 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
INCR OK to clear. |
| 10/21/2019 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
Corrections not made, another failed inspection will result in a reinspection fee. |
| 10/18/2019 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
Ground rods not properly installed, ground rods not to be installed diagonally. grounding conductors run through EMT must be bonded at both ends, provide two points of attachment to the structure at riser |