Permit: T19CM07318

Parcel: 125040980

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
10/20/2020 PLUMBING - FINAL Approved All five are approved.
10/05/2020 PLUMBING - FINAL Denied 1. Increase the size of the gas flex pipes, to the water heaters, to match the size of the gas hard pipe.
2. The kitchen island is required to have at least one GFI outlet.