Inspection History Details
Inspection Status: Approved
Inspection History: RESIDENTIAL INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/30/2019 | RESIDENTIAL INTERMEDIATE | Approved | ||
| 12/26/2019 | RESIDENTIAL INTERMEDIATE | Denied | 1- Shall provide water test on the DWV system. 2- Shall relocate the water line away from the truss gusset plate. 3- Shall seal all top plate penetrations with fire rated foam or caulk 4- Shall provide approved straps on condensate drain. 5- Shall provide water test on domestic water distribution. |
|
| 12/20/2019 | RESIDENTIAL INTERMEDIATE | Not ready for Inspection |