Permit: T19CM07239

Parcel: 110067400


Addresses:

2864 N FAIR OAKS AV


Inspection Status: Passed

Inspection History: COT - RSBU - Excavation/Rebar/Zoning 

Permit Number - T19CM07239

Inspection Description - COT - RSBU - Excavation/Rebar/Zoning 

Inspection Status - Passed

Date Description Inspector Results Comments
10/23/2019 COT - RSBU - Excavation/Rebar/Zoning  RCHANDLER Approved Entered by DMERANZ1 - Note: Fire walls added to this lot due to being too close to property lines.
10/17/2019 COT - RSBU - Excavation/Rebar/Zoning  RCHANDLER Correction Required Entered by DMERANZ1 - 1-The forms for this house will put the concrete six feet from the adjacent house; both walls are unrated with openings, which does not meet the requirements of IRC R Section R302.1 Exterior walls. REVISE Section by DELETING all text and tables (TABLE R302.1(1) EXTERIOR WALLS and TABLE R302.1(2) EXTERIOR WALLS-DWELLINGS WITH FIRE SPRINKLERS) and REPLACING with the following: Exterior walls with a fire separation distance less than 3 feet (914mm) shall have not less than a one- hour fire-resistive rating with exposure from both sides. Projections shall not extend to a point closer than 2 feet (610 mm) from the line used to determine the fire separation distance. Projections extending into the fire separation distance shall have not less than one-hour fire-resistive construction on the underside. The above provisions shall not apply to walls which are perpendicular to the line used to determine the fire separation distance.