Inspection History Details
Inspection Status: Passed
Inspection History: COT - RSBU - Excavation/Rebar/Zoning
Permit Number - T19CM07239
Inspection Description - COT - RSBU - Excavation/Rebar/Zoning
Inspection Status - Passed
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/23/2019 | COT - RSBU - Excavation/Rebar/Zoning | RCHANDLER | Approved | Entered by DMERANZ1 - Note: Fire walls added to this lot due to being too close to property lines. |
| 10/17/2019 | COT - RSBU - Excavation/Rebar/Zoning | RCHANDLER | Correction Required | Entered by DMERANZ1 - 1-The forms for this house will put the concrete six feet from the adjacent house; both walls are unrated with openings, which does not meet the requirements of IRC R Section R302.1 Exterior walls. REVISE Section by DELETING all text and tables (TABLE R302.1(1) EXTERIOR WALLS and TABLE R302.1(2) EXTERIOR WALLS-DWELLINGS WITH FIRE SPRINKLERS) and REPLACING with the following: Exterior walls with a fire separation distance less than 3 feet (914mm) shall have not less than a one- hour fire-resistive rating with exposure from both sides. Projections shall not extend to a point closer than 2 feet (610 mm) from the line used to determine the fire separation distance. Projections extending into the fire separation distance shall have not less than one-hour fire-resistive construction on the underside. The above provisions shall not apply to walls which are perpendicular to the line used to determine the fire separation distance. |