Permit: T19CM07219

Parcel: 137335480


Addresses:

1740 W PINERIVER PL

Inspection Status: Canceled

Inspection History: COT - LCBU - Framing

Date Description Inspector Results Comments
11/07/2022 COT - LCBU - Framing Canceled Inspection Canceled
12/03/2019 COT - LCBU - Framing TVALENCIA Denied Entered by DMERANZ1 - 1- Shall seal all top plate penetrations with fire rated foam or caulk. 2- Shall secure the electric conductors within 6 inches of the switch box at entry 3- Shall provide (3) sided blocking for the forced air vent.