Date Description Inspector Results Comments
12/17/2019 COT - RSEL - Construction Power MRAMBER Approved Entered by DMERANZ1 - ECO OK to clear.
12/11/2019 COT - RSEL - Construction Power MRAMBER Denied Entered by DMERANZ1 - No GEC., UFER has been removed since inspection, provide 2 ground rods, 8’ in length and a minimum 6’ apart.