Permit: T19CM07123

Parcel: 137310600

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
10/24/2019 MECHANICAL - FINAL Approved
10/22/2019 MECHANICAL - FINAL Denied 1- Shall provide locking caps on the condenser refrigerant service ports.
10/18/2019 MECHANICAL - FINAL Denied 1- Shall provide locking caps on the condenser refrigerant service ports.
2- The fuses should be40 amps. There is one 40 amp and one 45 amp.