Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 03/09/2020 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
ok for clearance INCR tep called at 10:20 |
| 01/28/2020 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
1- The gas bond shall be landed on the supply piping downstream of the meter and not on the service side. |
| 01/09/2020 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
200 amp panel not installed and gas bond on wrong side of meter |