Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING PRE-SLAB
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/01/2020 | BUILDING PRE-SLAB | Approved | approved 1- okay to pour footings and saw cut areas |
|
| 05/28/2020 | BUILDING PRE-SLAB | Denied | denied 1- The contact number on the permit is the previous General Contractor who is no longer on the job. There was no message given on the inspection request. |
|
| 03/12/2020 | BUILDING PRE-SLAB | Denied | 1- There are numerous locations where the masonry footing has less of 8 inches of concrete. Reference section R404 2018 IRC | |
| 03/03/2020 | BUILDING PRE-SLAB | Denied | 1- Shall remove all rocks out of plumbing trenches as requested and provide clean fill and proper compaction. There is numerous voids under the existing slab. 2- Shall expose exterior new footings for verification of the minimum 12 inches of footing depth at all corners and center of footings. 3- Shall provide a minimum of 4 inches of concrete at Shower. |