Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 09/19/2019 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
(RVI) |
| 09/18/2019 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
Breaker installed now is a 50 amp. The wire ran to service point is labeled 40 amp. Need to change breaker to 40 amp. Or replace wire with 50 amp wire. |