Inspection History: PLUMBING - GAS RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/03/2019 | PLUMBING - GAS RECONNECT | Approved | Clear gas for unit #7 | |
| 09/30/2019 | PLUMBING - GAS RECONNECT | Denied | 1. Gauge reads 8.2 lbs, in the sun at 10:15. Gauge must be between 10 and 15 lbs and stay where it starts. 2. Need carbon monoxide detector in hallway installed per manufacturers specs. 3. Need complex address #s visible from street. ANOTHER FAILED INSPECTION WILL RESULT IN A RE-INPSECTION FEE |
|
| 09/13/2019 | PLUMBING - GAS RECONNECT | Denied | 1. New gas water heater installed without permit and inspection. 2. Water heater gas feed line needs a drip leg. 3. TPR valve needs a drain line. 4. Water heater needs an enclosure. 5. B vent needs to be 3’ above the roof. 6. Pex cannot be exposed to sunlight. 7. New hose bib needs a back flow preventer. 8. Cut 3" abs cleanout to grade in rear yard. 9. Neighbors washer cannot drain into this units yard. 10. Need carbon monoxide alarm in hallway. |