Permit: T19CM06664

Parcel: 107110650

Inspection Status: Approved

Inspection History: PLUMBING - GAS RECONNECT

Date Description Inspector Results Comments
10/03/2019 PLUMBING - GAS RECONNECT Approved Clear gas for unit #7
09/30/2019 PLUMBING - GAS RECONNECT Denied 1. Gauge reads 8.2 lbs, in the sun at 10:15. Gauge must be between 10 and 15 lbs and stay where it starts.
2. Need carbon monoxide detector in hallway installed per manufacturers specs.
3. Need complex address #s visible from street.
ANOTHER FAILED INSPECTION WILL RESULT IN A RE-INPSECTION FEE
09/13/2019 PLUMBING - GAS RECONNECT Denied 1. New gas water heater installed without permit and inspection.
2. Water heater gas feed line needs a drip leg.
3. TPR valve needs a drain line.
4. Water heater needs an enclosure.
5. B vent needs to be 3’ above the roof.
6. Pex cannot be exposed to sunlight.
7. New hose bib needs a back flow preventer.
8. Cut 3" abs cleanout to grade in rear yard.
9. Neighbors washer cannot drain into this units yard.
10. Need carbon monoxide alarm in hallway.