Permit: T19CM06346

Parcel: 132130750


Addresses:

3300 S PARK AV

Inspection Status: Approved

Inspection History: BUILDING - PROGRESS

Date Description Inspector Results Comments
08/03/2020 BUILDING - PROGRESS Approved approved
05/08/2020 BUILDING - PROGRESS Partial Approval RVI Partial. Electric service panels 1H1, 1HV,1L1-1L4, 1LV, 1K1, 1K2, 1C1, I.T., & transformer 1TV
05/07/2020 BUILDING - PROGRESS Partial Approval partial
1- This inspection is for Service Panels 2H1,2H2,2L1,2L2,2L3,2L4,2L5, & 2L6 only. Okay to energize.
05/06/2020 BUILDING - PROGRESS Partial Approval RVI Partial. Transformers 1T2, 1T3, 2T2, 150 Iva; distribution boards 1LD2, 1LD3, 2LD2; H/V panels 1H2, 1H3. All ok to energize
05/05/2020 BUILDING - PROGRESS Partial Approval 1- This inspection was for the Electrical room 127. Transformers 1T1,2T1 and Feeder Panels 1LD1,2LD1 are okay to energize.