Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
Permit Number - T19CM06073
Inspection Description - ELECTRIC - RECONNECT
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/08/2020 | ELECTRIC - RECONNECT | Approved | ok for clearance RECN | |
| 08/26/2019 | ELECTRIC - RECONNECT | Correction Required | 1-Smoke detector in front bedroom is less than three feet from ceiling fan. 2-Cover plates in Master Bedroom are not installed. 3-Install smoke detectors and CO detectors per Code. 4-Wire furnace per code. Discussed items with builder as well as missing fire-blocks and hardwiring smoke detectors and CO detector for future inspections. Builder will disconnect all circuits except kitchen and request 2060 Electric Temporary Power inspection to get power for the job. Note: Recommended remote inspection for 2060 Electric Temporary Power when ready. |