Inspection Status: Canceled
Inspection History: COT - FCON - Fire - Final
| Date |
Description |
Inspector |
Results |
Comments |
| 11/07/2022 |
COT - FCON - Fire - Final |
|
Canceled |
Inspection Canceled |
| 10/08/2019 |
COT - FCON - Fire - Final |
MRoss |
Partial Approval |
Entered by MROSS2 - Ok to obtain TCO
-Remove non required fire alarm system or have it inspected and placed in service, this would include hood connection to FA.
-Repair or replace emergency light over north lobby door. |
| 10/08/2019 |
COT - FCON - Fire - Final |
MROSS |
Partial Approval |
Entered by PMARTIN1 - PA/OK FOR TCO SENT TO RECORDS |
| 10/04/2019 |
COT - FCON - Fire - Final |
jvincent |
Denied |
Entered by JVINCEN1 - -Some EM lights and exit signs not working. Need to test all during reinspection.
-Remove all gate latches and hardware from front pation gates.
-Provide/install/mount class K extinguisher.
-Obtain operational permit for places of assembly.
-Mount OL sign in lobby.
-Remove nonrequired FA system and all components including all wiring and mircro switch for hood system.
-Electric behind hood did not shut off during trip test. Must shut off.
-Fryer shield x 2 required since you have burners on both sides of fryer.
-Submit revised set of hood plans. Cook lineup is different than plans. |