Permit: T19CM06072

Parcel: 11310023A

Inspection Status: Canceled

Inspection History: COT - FCON - Fire - Final

Date Description Inspector Results Comments
11/07/2022 COT - FCON - Fire - Final Canceled Inspection Canceled
10/08/2019 COT - FCON - Fire - Final MRoss Partial Approval Entered by MROSS2 - Ok to obtain TCO -Remove non required fire alarm system or have it inspected and placed in service, this would include hood connection to FA. -Repair or replace emergency light over north lobby door.
10/08/2019 COT - FCON - Fire - Final MROSS Partial Approval Entered by PMARTIN1 - PA/OK FOR TCO SENT TO RECORDS
10/04/2019 COT - FCON - Fire - Final jvincent Denied Entered by JVINCEN1 - -Some EM lights and exit signs not working. Need to test all during reinspection. -Remove all gate latches and hardware from front pation gates. -Provide/install/mount class K extinguisher. -Obtain operational permit for places of assembly. -Mount OL sign in lobby. -Remove nonrequired FA system and all components including all wiring and mircro switch for hood system. -Electric behind hood did not shut off during trip test. Must shut off. -Fryer shield x 2 required since you have burners on both sides of fryer. -Submit revised set of hood plans. Cook lineup is different than plans.