Permit: T19CM05998

Parcel: 14041059A


Addresses:

3265 E UNIVERSAL WY

Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Date Description Inspector Results Comments
05/15/2020 FIRE - ALARM FINAL Approved approved 5/15/20
04/07/2020 FIRE - ALARM FINAL Denied notification devices did not synchronize, check voltage at EOL to see if the draw is over drawing. Fire alarm shall shut down the music system throughtout the building. If power supplies are added submit and pay for re-submittals. Work drawn and perfromed by Firetrol is approved. Cintas performed the repairs as requested and they need to submit fire alarm plan and test the fire alarm per the items listed above.