Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/15/2020 |
FIRE - ALARM FINAL |
|
Approved |
approved 5/15/20 |
| 04/07/2020 |
FIRE - ALARM FINAL |
|
Denied |
notification devices did not synchronize, check voltage at EOL to see if the draw is over drawing. Fire alarm shall shut down the music system throughtout the building. If power supplies are added submit and pay for re-submittals. Work drawn and perfromed by Firetrol is approved. Cintas performed the repairs as requested and they need to submit fire alarm plan and test the fire alarm per the items listed above. |