Inspection History Details
Inspection Status: Denied
Inspection History: PLUMBING - GAS RECONNECT
Permit Number - T19CM05941
Inspection Description - PLUMBING - GAS RECONNECT
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/20/2019 | PLUMBING - GAS RECONNECT | Denied | 1- Shall provide a air pressure test on the entire system 10 lbs. minimum 2- Shall lift and support the 1/2 inch gas line to the Gas pack unit a minimum of 3 inches above the sub grade. 3- Shall provide a sediment trap at Gas pack unit. 4- Shall open the water heater door at the time of inspection. |
|
08/20/2019 | PLUMBING - GAS RECONNECT | Approved | Clear gas meter Verbal clearance called in at 3:09 pm |