Permit: T19CM05941

Parcel: 10706002D

Inspection Status: Denied

Inspection History: PLUMBING - GAS RECONNECT

Permit Number - T19CM05941

Inspection Description - PLUMBING - GAS RECONNECT

Inspection Status - Denied

Date Description Inspector Results Comments
08/20/2019 PLUMBING - GAS RECONNECT Denied 1- Shall provide a air pressure test on the entire system 10 lbs. minimum
2- Shall lift and support the 1/2 inch gas line to the Gas pack unit a minimum of 3 inches above the sub grade.
3- Shall provide a sediment trap at Gas pack unit.
4- Shall open the water heater door at the time of inspection.
08/20/2019 PLUMBING - GAS RECONNECT Approved Clear gas meter Verbal clearance called in at 3:09 pm