Permit: T19CM05898

Parcel: 110051250

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/01/2019 ELECTRIC - FINAL Approved
10/25/2019 ELECTRIC - FINAL Correction Required 1-Separate neutrals from grounds at sub-panel per IRC E3607.2. 2-Label panels per IRC E3706.2. 3-Protect conductors from abrasion at field cuts to dead front in service per IRC E 3404.7.