Permit: T19CM05846

Parcel: 140260360

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
10/23/2019 PLUMBING - INTERMEDIATE Approved (rvi)
10/18/2019 PLUMBING - INTERMEDIATE Denied 1- Shall locate the horizontal revent a minimum of 6 inches above the flood level rim of the fixture.
2- Can not reduce then increase the size of the vent for the floor sink.