Permit: T19CM05841

Parcel: 112062610


Addresses:

2019 E SILVER ST 2

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
10/14/2019 ELECTRIC - SERVICE UPGRADE Approved Clear incr to move meters from front house to new panels on rear house.
10/08/2019 ELECTRIC - SERVICE UPGRADE Correction Required 1--Bond gas piping.
2-Expose grounding electrode conductor and the connection of it to both ground rods.
3-Service for unit one needs to have Grounding Electrode Conductor connected directly to Grounding Electrodes per IRC E3607.4; can not connect to other service.