Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/14/2019 | ELECTRIC - SERVICE UPGRADE | Approved | Clear incr to move meters from front house to new panels on rear house. | |
| 10/08/2019 | ELECTRIC - SERVICE UPGRADE | Correction Required | 1--Bond gas piping. 2-Expose grounding electrode conductor and the connection of it to both ground rods. 3-Service for unit one needs to have Grounding Electrode Conductor connected directly to Grounding Electrodes per IRC E3607.4; can not connect to other service. |