Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T19CM05544
Inspection Description - FIRE - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/08/2022 | FIRE - FINAL | Approved | ||
| 03/30/2022 | FIRE - FINAL | Partial Approval | Ok to occupy the first floor and the basement per tucson fire, 1. Fix coverage in the elevator lobby on the first floor. 2. unit 2005 has a croocked head needs to be corrected, 3.need head in unit 1001. 4. add skirts on heads in the bathrooms fire alarms 1. need to test duct detectors 2. fix address lables on zone 3 3. document box needs to be installed next to the panel 4. lockout at breaker for the fire alarm needs to be red and labled. need to add sign on riser room door stating FACP. |