Permit: T19CM05086

Parcel: 12704001B


Addresses:

4900 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
07/19/2019 PLUMBING - GAS PRESSURE TEST Approved Needs PDSD
SW Gas Clearance, Reconnect

SW Gas Was Called for Clearance, Reconnect, June. Done
07/17/2019 PLUMBING - GAS PRESSURE TEST Denied 1- Shall provide a Mechanical Engineer to assess the existing gas system and provide direction on how to eliminate water residue that was introduced to the gas system due to the plumbing contractor connecting the gas system to the domestic water distribution.
2- Shall submit the Engineers written response with direction to the Building Official for approval.