Inspection History Details
Inspection Status: Not Ready
Inspection History: COT - HCBU - Building Final
Permit Number - T19CM05078
Inspection Description - COT - HCBU - Building Final
Inspection Status - Not Ready
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/26/2022 | COT - HCBU - Building Final | Not Ready | ||
05/20/2022 | COT - HCBU - Building Final | ESTEVENS | Partial Approval | Entered by RSALDAT1 - Partial. Pending other inspections. |
05/09/2022 | COT - HCBU - Building Final | ESTEVENS | Partial Approval | Entered by VVERA1 - Partial. Approved for C of O for state inspection. |
05/06/2022 | COT - HCBU - Building Final | ESTEVENS | Not ready for Inspection | Entered by RSALDAT1 - Not ready |
05/05/2022 | COT - HCBU - Building Final | ESTEVENS | Cancelled | Entered by NGARCIA3 - Canceled by contractor, Lance. |
05/03/2022 | COT - HCBU - Building Final | ESTEVENS | Partial Approval | Entered by NGARCIA3 - Partial. CEP area. Label all piping and valves. Seal all holes in ceiling. Remove wedge and fire caulk all penetrations in chiller room. Label electrical panels in chiller room. Finish wiring exhaust fan. Missing glazing on fire doors. |
04/25/2022 | COT - HCBU - Building Final | ESTEVENS | Cancelled | Entered by NGARCIA3 - Canceled by contractor, Lance. |
04/15/2022 | COT - HCBU - Building Final | ESTEVENS | Partial Approval | Entered by VVERA1 - Partial. Level one. Area C. and Level D |
04/14/2022 | COT - HCBU - Building Final | ESTEVENS | Partial Approval | Entered by NGARCIA3 - Partial. Level one. Area A and Area B. |
04/13/2022 | COT - HCBU - Building Final | ESTEVENS | Partial Approval | Entered by VVERA1 - Partial. Level two. Areas A, B, AND C. |