Permit: T19CM05054

Parcel: 13216600A


Addresses:

4004 S PARK AV 08


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T19CM05054

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
10/18/2019 ELECTRIC - INTERMEDIATE Approved
10/05/2019 ELECTRIC - INTERMEDIATE Partial Approval Inspection for Interconnection of PV system to Existing 1600AMP transfer Switch. From 277/480V, 400AMP PV Utility Disconnect. 2 Parallel sets of 4/0 Cu ungrounded Conductors, 2AWG Neutrals, 2AWG Grnds. Third party on site to perform Hi-pot test & all test were Approved.