Permit: T19CM04987

Parcel: 141365970

Inspection Status: Approved

Inspection History: STEM WALL/RETAINING WALL

Permit Number - T19CM04987

Inspection Description - STEM WALL/RETAINING WALL

Inspection Status - Approved

Date Description Inspector Results Comments
08/07/2019 STEM WALL/RETAINING WALL Approved
08/01/2019 STEM WALL/RETAINING WALL Not ready for Inspection bond beam is not completed all the way to the southernmost edge. Missing weep holes, drawing call for them to be 6 foot on center and 12 inches below top of retaining wall. Control joints are either not cut all the way through or done incorrectly and are not per drawing, also need to be 16 feet on center. Footing will need to be cleaned up for waterproofing and P gravel will need to be looked at before backfilling wall. Please follow drawing before recalling in the inspection.