Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T19CM04976
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/03/2020 | FIRE - FINAL | Approved | ||
01/31/2020 | FIRE - FINAL | Partial Approval | THIS IS FOR BOOTH ONLY. NOT BLDG. contact is Jake 631-3266 -Need sprink final. See notes. -Cannot use "fire" horn/strobes for gas detection alarm. -Remove slide bolts from door. |