Permit: T19CM04900

Parcel: 132090120

Inspection Status: Correction Required

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/23/2019 ELECTRIC - FINAL Correction Required The Grounding Electrode Conductor for 3051 E Proctor Vista has been compromised in the process of Grounding 3049 E Proctor Vista ( these addresses share a weather head and lateral conductors). The water bond for both services has also been installed improperly. Install Code compliant Grounding Electrode Conductor for 3051 E Proctor Vista and a Code Compliant water bond for both services.
07/12/2019 ELECTRIC - FINAL Correction Required 1-Install all devices with covers, or cover boxes.
2-Panel at service is not listed for wet location.
3-Need to install smoke detectors per Code.
4-Install grounding electrode conductor and connect it to ground rods per Code.