Permit: T19CM04784

Parcel: 124110510


Addresses:

1715 E MILES ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
08/15/2019 PLUMBING - FINAL Approved complete previous correction of screws in b venting no tape please.
08/12/2019 PLUMBING - FINAL Not ready for Inspection previous corrections not fixed correctly. Piping for T&P needs to be hard piped copper or galvanized 6 inches from finish floor. Flu venting not secured correctly. Missing shut off. 18 inches of copper piping required from shut off before changing to pex.
08/09/2019 PLUMBING - FINAL Correction Required Complete termination for and P valve.
Clearance SWG, OK to connect.
08/08/2019 PLUMBING - FINAL Not ready for Inspection Contractor cancelled, will reschedule for 9 August.