Permit: T19CM04764

Parcel: 13216600A


Addresses:

4004 S PARK AV 10

Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Date Description Inspector Results Comments
10/14/2019 ELECTRIC - UNDERGROUND Approved
10/01/2019 ELECTRIC - UNDERGROUND Partial Approval 1- Underground electric conduits are okay to cover from the last advance location of conduits up to the light pole directly South of SE corner of bldg. G only.
09/20/2019 ELECTRIC - UNDERGROUND Partial Approval Underground electric conduits are okay to cover from the pull box to the midway point to bldg. only.
09/17/2019 ELECTRIC - UNDERGROUND Partial Approval 1- Underground electric conduits are okay to cover from the second pull box to fence/median.
09/05/2019 ELECTRIC - UNDERGROUND Partial Approval 1- Underground electric conduits from South side of bldg. 2 Bay W East to the East side of main access road medium is okay to cover.
09/04/2019 ELECTRIC - UNDERGROUND Partial Approval 150 feet west of the panelboard.
08/30/2019 ELECTRIC - UNDERGROUND Partial Approval 1- Underground electric conduits are okay to cover from Canopy A to the panel board only.