Permit: T19CM04702

Parcel: 118041330

Inspection Status: Approved

Inspection History: RESIDENTIAL INTERMEDIATE

Date Description Inspector Results Comments
08/17/2019 RESIDENTIAL INTERMEDIATE Approved
08/08/2019 RESIDENTIAL INTERMEDIATE Denied 1- Electric in walls and at sub panel is okay.
2- Shall provide (3) sided blocking on all forced air vents.
3- Shall secure the horizontal pex water lines every 32 inches.
4- Shall is install the garden tub.
5- Washing machine stand pipe shall be a minimum of 18 inches maximum 42 inches.
6- Washing Machine trap arm distance to be a minimum of two times the pipe diameter.
7- Provide a water test on DWV system.
8- Gas pressure test to be at 10 lbs. minimum.
9- A threaded joint at Washing Machine p- trap can not be located in a concealed location.