Inspection History Details
Inspection Status: Approved
Inspection History: RESIDENTIAL INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/17/2019 | RESIDENTIAL INTERMEDIATE | Approved | ||
| 08/08/2019 | RESIDENTIAL INTERMEDIATE | Denied | 1- Electric in walls and at sub panel is okay. 2- Shall provide (3) sided blocking on all forced air vents. 3- Shall secure the horizontal pex water lines every 32 inches. 4- Shall is install the garden tub. 5- Washing machine stand pipe shall be a minimum of 18 inches maximum 42 inches. 6- Washing Machine trap arm distance to be a minimum of two times the pipe diameter. 7- Provide a water test on DWV system. 8- Gas pressure test to be at 10 lbs. minimum. 9- A threaded joint at Washing Machine p- trap can not be located in a concealed location. |