Permit: T19CM04605

Parcel: 122182980


Addresses:

3506 E PIMA ST

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
09/20/2019 PLUMBING - ROUGH, SOIL Approved (RVI)
09/05/2019 PLUMBING - ROUGH, SOIL Not ready for Inspection Corrections not completed.. Note: If this inspection is not approved next time, a re-inspection fee will be assessed.
Note: This inspection is a good candidate for remote inspection.
08/16/2019 PLUMBING - ROUGH, SOIL Correction Required Pothole lines that are now buried, expose tracer wire, and put test on piping.
08/14/2019 PLUMBING - ROUGH, SOIL Cancelled Cancelled by Amado on phone.
07/09/2019 PLUMBING - ROUGH, SOIL Partial Approval Under slab is approved. Tie in to existing HCS outside remains to be inspected.
07/08/2019 PLUMBING - ROUGH, SOIL Denied Not under water test.
07/03/2019 PLUMBING - ROUGH, SOIL Correction Required Vent fittings still being used for drainage.
07/02/2019 PLUMBING - ROUGH, SOIL Correction Required Green tracer wire required on all Building Drain to Sewer lines outside the building.

As discussed, Vent fittings are not approved for use as drainage fittings.