Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/12/2019 | ELECTRIC - RECONNECT | Approved | Angel, Owner in contact with TEP. TEP will be out around 8-3-2019 to clean up their boxes and feeders. TEP Clearance, RECN |
|
| 06/25/2019 | ELECTRIC - RECONNECT | Correction Required | 1-Service disconnect needs to be lowered so that the handle complies with NEC240.24A. 2-Service is mounted to plywood that is unprotected from weather, and thus subject to dilapidation; re- mount on Code approved manner. 3-Remove all unused wiring. 4-Remove or re-wire to Code All lighting. 5-Close all unused openings. |