Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T19CM04466
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/30/2019 | PLUMBING - INTERMEDIATE | Approved | ||
08/27/2019 | PLUMBING - INTERMEDIATE | Cancelled | Canceled by contractor | |
08/23/2019 | PLUMBING - INTERMEDIATE | Denied | 1. Pex lines need to be tested at 50psi minimum for 15 minutes, Air pressure gauge read 35psi at time of inspection ANOTHER FAILED INSPECTION MAY RESULT IN REINSPECTION FEES |
|
08/20/2019 | PLUMBING - INTERMEDIATE | Denied | 1. Potable water lines not under test 2. Need both tubs filled 3. Secure toilet flanges |