Permit: T19CM04466

Parcel: 14032087A


Addresses:

4011 E LIMELIGHT PL


Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T19CM04466

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
08/30/2019 PLUMBING - INTERMEDIATE Approved
08/27/2019 PLUMBING - INTERMEDIATE Cancelled Canceled by contractor
08/23/2019 PLUMBING - INTERMEDIATE Denied 1. Pex lines need to be tested at 50psi minimum for 15 minutes, Air pressure gauge read 35psi at time of inspection
ANOTHER FAILED INSPECTION MAY RESULT IN REINSPECTION FEES
08/20/2019 PLUMBING - INTERMEDIATE Denied 1. Potable water lines not under test
2. Need both tubs filled
3. Secure toilet flanges