Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/25/2019 | FIRE - FINAL | Approved | ||
| 09/17/2019 | FIRE - FINAL | Partial Approval | -Need FDC sign with arrow mounted on south side of bldg. -FACP sign on office door. -Repair exit sign/em light top of stairs. -Outlets D20 and outlet to the north of D20, under hood, need shunt trip. Did not trip upon hood activating. -Need junction box cover plate for tamper switch on riser (exposed electrical). |