Inspection Status: Passed
Inspection History: COT - LCPL - Plumbing Intermediate
| Date |
Description |
Inspector |
Results |
Comments |
| 11/18/2019 |
COT - LCPL - Plumbing Intermediate |
DMUNIZ |
Approved |
Entered by DMERANZ1 - All corrections have been made, ok to proceed.
|
| 11/15/2019 |
COT - LCPL - Plumbing Intermediate |
MRAMBER |
Denied |
Entered by DMERANZ1 - UFER Not properly attached. Anchor bolts missing at garage opening. Provide minimum clearance from B vent to combustibles. Duct branch fittings and Plenum’s not properly insulated. Duct pinched or compressed through trusses. Provide full radius bends at flex duct, choking at boot boxes not acceptable. Bathtub fitting leaking. Condensate piping penetrating top plate not sealed. Condensate piping draining uphill. Exhaust fans missing out laundry. Inspections stopped at this time this is not a complete list. |