Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T19CM04364
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/15/2019 | FIRE - FINAL | Approved | will follow up on signage, FDC plugs, knox box. | |
11/14/2019 | FIRE - FINAL | Partial Approval | 1. Ok for TCO for occupancy and open to the public. 2. Need to test hoodless fryers. 3. Add Locking FDC caps to FDC. 4. Install Knox Box and install keys. 5. Install 15in. address numbers to exterior. 6. Place FACP sign on FACP room door. |
|
10/29/2019 | FIRE - FINAL | Denied | Looking to get TCO for stocking. Informed them that the sprinkler system shall be active in order to do so. Kazal is sub doing work. * Informed that one sprinkler head shall be added on main floor on east side of building. * All sprinkler heads shall be installed prior to approval and caps removed. * Insulation shall not be sitting on top of sprinkler heads. Re-inspection fee will be added. |
|
10/24/2019 | FIRE - FINAL | Compliance | Calling in Fire final because there is no Fire immediate for consult. Willing to pay extra fee for extra inspection, just wants to make sure everything is covered. |