Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 07/12/2019 |
MECHANICAL - INTERMEDIATE |
|
Approved |
|
| 07/10/2019 |
MECHANICAL - INTERMEDIATE |
|
Denied |
Gas piping not properly supported or anchored, condensate piping to be supported a minimum 3 1/2 inches above roof, coated For UV protection and must terminate within 6 inches of grade. |